Main features
Process inputs:
1 universal input
- Thermocouples: L, J, T, K, S, R, B, N, E, Ni-NiMo, W3, W5
- RTD: Pt100
- Voltage (mV):0/10...50 mV
- Current (mA): 0/4...20 mA (with 2.5 Ω shunt resistor)
- Custom linearisation and IR probes (J.K type)
Accuracy : 0.25% ±1 digit (probes) or 0.1% ±1 digit (mA or mV)
1 digital input
- NPN
- TTL
- Free Voltage
Process outputs:
1 High level analogue output:
- For PV retransmission (optional)
- Current (mA): 0/4...20 mA
4 Digital outputs:
OUT1
- RELAY SPST-NO, 2A (250VAC)
- TRIAC 1A 250 VAC
OUT2
- RELAY SPST-NO, 2A (250VAC)
- TRIAC 1A 250 VAC
Power supply:
- 24VDC/VAC
Transmitter power supply: 18 Vdc ±20%, 30 mA Max
Functions:
- Acquisition and retransmission
- Configuration and parameters back-up and automatic restore
(with DX master)
Alarms:
- Up to 3 configurable alarms (third one only on serial com.)
Communication and programming:
Interfaces:
- RS 485 port with ModBus RTU and J-bus (slave) protocols
Programming/configuration tools:
- Configuration software available for PC
Installation:
Mounting method: DIN rail mount
Case dimensions: 22.5 x 99 mm, depth 114.5 mm
Connections:
Communication ports:
- RS485 on male and female side bus connection
Signals connection:
- 4 Extractable polarized 4 pole screw plugs , 2.5 mm²
- Withdrawable electronic without un-wiring signals,
power supply and communication bus
Connectable to:
- Deltadue Series
- SCADA for monitoring, traceability and remote management
- DX and DY gateways for remote monitoring
Just some of possible applications:
- Extruders
- Multiloop data acquisition and process control
Ascon Tecnlogic