DA561 transmitter – Inor
Isolation transmitter for mA/V signals with 2-wire transmitter supply – Inor
DA561 is specially designed for signal isolation and load amplification in the process industry.
A 2-wire transmitter can be connected to and supplied from the isolation amplifier. DA561 maintains a high isolation level (1,5 kV) between input and output. Current and voltage can be chosen independently as input and output signals.
Features
- Current and voltage input
- Current and voltage output
- Direct connection of 2-wire transmitter
- Output test terminals
- 1 500 V isolation level
- Short response time
- High noise immunity
- Available for AC or DC power supply
- DIN-rail mounting
- Plug-in screw terminals
Properties
- Input voltage: 0(0,2)-1 V, 0(1)-5 V, 0(2)-10 V
- Input impedance: 1 MΩ
- Input current: 0(4)-20 mA (standard setting)
- Input impedance: 11,9 Ω
- Maximum input level: 200 % of measurement span
- Output voltage: 0(0,2)-1 V, 0(1)-5 V, 0(2)-10 V, short circuit protected
- Minimum load: 500 kΩ (error effect)
- Voltage limitation: Approx. 56 V
- Output Current: 0(4)-20 mA, open or short circuit protected (standard setting)
- Maximum load: 600 Ω
- Current limitation: Approx. 23 mA
- Test output: mA instrument, Ri ≤ 10 Ω
- Transmitter supply voltage: 19 VDC, max. ripple 100 mV p-p
- Operation temperature: -20 to +60 °C / -4 to +140 °F
- Galvanic isolation AC & DC version:
- Input to output 1 500 VAC, 1 min
- Input/output to power supply 2 200 VAC, 1 min
- Power supply AC versions:
- 230 VAC, -15..+10 %, 45..75 Hz,
- 115 VAC, -15..+10 %, 45..75 Hz
- Power supply DC version: 19 to 60 VDC
- Typical accuracy: ±0,15 % of span
- Connections: Plug-in terminals Stranded, ≤ 2.5 mm2, AWG 14
- Mounting: Rail acc. to DIN EN 50022, 35 mm